Who owns a private power pole in Victoria, when a replacement must go underground, and what Powercor publishes for underground power connection costs.
In Victoria, the power pole cost you carry depends on which side of the point of supply the pole sits. Poles on the network side belong to Powercor or AusNet, but every pole and wire from the point of supply to your house is a private electric line, and you pay to maintain, repair and replace it. In a Hazardous Bushfire Risk Area, a private line that needs major repair must usually go underground. Powercor's published guide prices a 230 volt underground cable and pit off an existing overhead line at $6,543 for 10 metres and $17,772 for 50 metres, including GST at April 2024 prices, and your own side of the job comes on top.
Who owns the power pole on my property?
If a pole sits on your side of the point of supply, you own it. Energy Safe Victoria describes the point of supply as the changeover from the distribution network to your electrical installation, and says the owner is responsible for maintaining and repairing the installation, private electric lines included, from that point on.
Energy Safe calls these lines private aerial lines, or PALs, and you will still see the older name POEL (private overhead electric line) on distributor letters and forms. AusNet puts it simply: a private line starts at the first pole on your property and includes the lines, poles and fittings after it. A single span from the street straight to the house is called a private service line. If you are not sure where your point of supply is, ask your distributor before you buy anything.
What does a private power pole owner have to do?
You must keep the line in safe working condition and keep trees clear of it. Energy Safe recommends at least 1 metre of clearance from insulated service lines and 2 metres from bare wires, and says to use an experienced vegetation contractor where trees are closer than that or a branch could fall onto the line.
The distributor inspects your line for you on a fixed cycle. Energy Safe says the interval is normally no later than 37 months, or in some cases up to five years. Powercor says it inspects private electric lines every three years. AusNet says every three years in high bushfire risk areas and every five years in low risk areas. If the inspector finds a defect, you get a written defect notice with a date to fix it by. Energy Safe notes that ignored notices can be escalated to the regulator and an unsafe line can be disconnected.
AusNet also asks owners to look over their own line at least once a year. Binoculars from the ground are enough to spot a leaning pole, a split crossarm or a branch resting on the wire.
When does a private power pole replacement have to go underground?
When the job is big, or the property is in a Hazardous Bushfire Risk Area. Powercor says that, unless alternative compliance applies, undergrounding is mandatory if more than 20 per cent of the poles, spans or wires need repair or replacement, or if the line is in a Hazardous Bushfire Risk Area declared by the CFA.
Energy Safe's rules add three points worth knowing:
- In a Hazardous Bushfire Risk Area, a private line that needs substantial reconstruction, generally more than 20 per cent of spans or poles, must be placed underground.
- No private aerial line can be built or substantially reconstructed in an Electric Line Construction Area.
- After an emergency repair to restore power in a Hazardous Bushfire Risk Area, the owner signs an undertaking to put the line underground within 60 days, lodged with Energy Safe within 5 business days of the work.
Energy Safe can grant an exemption to keep a line overhead under regulation 701, after an application and assessment. Don't plan around getting one. The practical lesson is that the cheap fix, replacing one rotten pole, is only available while the rest of the line is sound. A line left until several poles fail can turn into a full underground job.
How much does an underground power connection cost?
Nobody publishes a price for your side of the boundary, because it depends on distance, ground and what is in the way. What Powercor does publish is its Customer's Selection Guide of indicative costs for typical minor projects, prices at April 2024, including GST:
- 230 volt cable and pit off an existing overhead low voltage line, up to 10 metres, excluding road boring: $6,543
- The same, up to 50 metres: $17,772
- 230 volt cable and pit in an underground estate, up to 30 metres: $10,934, or $13,949 with road boring
- Rural high voltage extension up to 250 metres underground, single phase with a substation: $181,806
Those figures cover Powercor's work. Powercor's private lines page says a conversion needs your registered electrical contractor to set up a new point of supply with Powercor, which may need an underground service pit. Then you pay for the trench, conduit and consumer mains from the pit to your switchboard, plus any tree clearing and removal of the old poles. Our Powercor connection cost page sets out the rest of that guide and what it leaves out.
What drives the cost of power pole installation?
The same handful of things, whether it is a new private pole, a replacement or an underground run:
- Distance. Every metre of trench or every extra span adds cable, conduit and labour.
- Ground. Rock, a creek crossing or a sealed driveway can cost more than the cable.
- Access. A pole needs a truck to reach it. A steep or soft block slows everything down.
- Trees. Clearing along the route is at your expense, and Powercor says the same for stump and debris removal on a new line.
- Cable size. A long run or a three phase supply needs heavier cable to keep the voltage up at the house.
- Bushfire area. In a Hazardous Bushfire Risk Area, overhead may not be an option at all.
Is there help to pay for undergrounding a private line?
Sometimes. Energy Safe says funding may be available from time to time for undergrounding private aerial lines and points owners to the Department of Energy, Environment and Climate Action. Past Victorian grant rounds covered private lines in designated bushfire risk areas within participating council areas, and we could not confirm that a round is open as at November 2026. Ask the department before you sign anything, because a grant usually has to be approved before the work starts.
What can an owner check safely, and what needs an electrician?
You can look, from a safe distance. Check for leaning or cracked poles, loose or sagging wires, crossarms that have split, and trees growing toward the line. Before digging deeper than 300 millimetres anywhere, Energy Safe says to contact Before You Dig Australia, and to contact your distributor before digging 900 millimetres or deeper within 1,500 millimetres of a pole.
Never climb a pole, prune near a live line or touch a fallen wire. Repairs to a private line are done by a licensed electrician or registered electrical contractor, and Energy Safe says the distributor reconnects a repaired line only once a Certificate of Electrical Safety is issued. Work on or near the distributor's own assets needs its written permission.
When is off grid worth pricing instead?
When the private line is long, runs through timber or now has to go underground, it is worth asking what the same money would do if the line were removed. Taking a house off the grid is a real option in Victoria, and our article on taking a grid connected house off grid explains how. Our page on off grid or a grid connection sets out where each one wins.
Mick McDonald
Technical Director, Trentham Energy
Questions about your own system? Call 1300 3458 00 or send us a message.